These
internal resistance baseline values from Alber research, battery
manufacturers, and our customers will help determine the health of your
batteries.
The average values
in micro-ohms, taken on known-good batteries at 100% capacity, are to be
used as guidelines only. Alber recommends you maintain baseline readings
for your batteries based on manufacturers' data.
Taking
Readings
When you take readings, you should record: Internal cell resistance;
measuring instrument used, such as the Cellcorder; battery manufacturer,
model and size (Ah); battery age; install date; date of test; and room
temperature.
The batteries
you measure should be either on-line or on-charge for at least 90 days.
Connect the measuring instrument to the battery according to the equipment
manufacturer's instructions, and observe the safety precautions below.
Listed
readings are based on tests done at room temperature, typically 77F. Alber
has observed that only extreme temperature variations affect cell
resistance readings.
Contributing
Your Readings
We would be pleased to add your resistance readings on 20 or more healthy
batteries to our database. Your data should show: Internal cell resistance;
measuring instrument used; battery manufacturer, model and size (Ah);
battery age; install date; date of test; and room temperature. Or, if you
have a Battery Analysis System ADF file, we can extract the data. To
contribute your readings, contact our Engineering department or e-mail the ADF file.
Downloading
a BLF File
You may download a file that contains resistance reference values for your
CRT-300. This BLF
battery list file for the Cellcorder BAS program has baseline data
searchable by manufacturer and model number. If you already have battery
baseline data, you should download then import the file, so your existing
baseline data is not overwritten.
Safety Precautions
Hazardous
voltages and chemicals may exist on batteries and in battery rooms and
cabinets. Only qualified, properly trained personnel should conduct
measurements on any battery. Always observe electrical safety precautions.
Always wear safety glasses and protective clothing when required.
The values are subject to change as new data is received.
Before measuring your batteries, read the safety precautions.
Internal Resistance
Baseline Values
|
Manufacturer
|
Cell Model
|
Average
Resistance
(micro-ohms)
|
|
Alcad
|
|
|
|
Alcad
|
H22P
|
2331
|
|
Alcad
|
SD-5
|
1412
|
|
Alcad
|
SD-13
|
533
|
|
Alcad
|
XHP 28
|
1186
|
|
Alcad
|
XHP 36
|
775
|
|
Alcad
|
XHP 90
|
507
|
|
Americad
|
|
|
|
Americad
|
HED-30
|
1841
|
|
C&D
|
|
|
|
C&D
|
3DCU-5
|
2987
|
|
C&D
|
4LC-YC11
|
236
|
|
C&D
|
GC12V75A
|
6046
|
|
C&D
|
KRC-15
|
253
|
|
C&D
|
LS12-100
|
3666
|
|
C&D
|
MCT4000
|
100
|
|
C&D
|
TEL12-90
|
4237
|
|
C&D
|
TEL12-105F
|
4523
|
|
C&D
|
TEL12-125
|
3774
|
|
C&D
|
UPS12-100FR
|
8601
|
|
C&D
|
UPS12-140FR
|
6332
|
|
C&D
|
UPS12-170FR
|
7038
|
|
C&D
|
UPS12-225
|
5133
|
|
C&D
|
UPS12-270FR
|
4124
|
|
C&D
|
UPS12-300
|
3117
|
|
C&D
|
UPS12-370FR
|
3497
|
|
C&D
|
UPS12-475FR
|
3887
|
|
C&D
|
XT2LC23
|
128
|
|
C&D
|
XT4LC15
|
174
|
|
Caterpillar
|
|
|
|
Caterpillar
|
9G4231
|
3457
|
|
Caterpillar
|
9X9720
|
4858
|
|
DEKA East
Penn
|
|
|
|
DEKA / East Penn
|
3AVR-85-23
|
263
|
|
DEKA / East Penn
|
3AVR-85-33
|
204
|
|
Douglas
|
|
|
|
Douglas
|
DGS12-150F
|
3183
|
|
Enersys
|
|
|
|
EnerSys
|
HR300
|
4181
|
|
EnerSys
|
HR500
|
3145
|
|
Exide
|
|
|
|
Exide
|
2DX-19
|
137
|
|
Exide
|
2GU-13
|
264
|
|
Exide
|
3CC-5
|
1688
|
|
Exide
|
EA-13
|
321
|
|
Exide
|
EC-19
|
221
|
|
Exide
|
ES-21
|
202
|
|
Exide
|
EU-7
|
664
|
|
Exide
|
GU-45
|
102
|
|
Fiamm
|
|
|
|
Fiamm
|
Monolite 45L8150
|
1458
|
|
GNB
|
|
|
|
GNB
|
90A13
|
427
|
|
GNB
|
90A21
|
215
|
|
GNB
|
100A33
|
180
|
|
GNB
|
100A87
|
191
|
|
Johnson
Controls
|
|
|
|
Johnson Controls
|
FRB12-300
|
3994
|
|
Johnson Controls
|
GC12V75A
|
6046
|
|
Johnson Controls
|
UPS12-140FR
|
6332
|
|
Johnson Controls
|
UPS12-170FR
|
7038
|
|
Johnson Controls
|
UPS12-270FR
|
4124
|
|
Johnson Controls
|
UPS12-300
|
3117
|
|
Johnson Controls
|
UPS12-310FR
|
3324
|
|
Johnson Controls
|
UPS12-370FR
|
3497
|
|
Power
|
|
|
|
Power
|
PL-15
|
1996
|
|
Power
|
PRC-1225X
|
12908
|
|
Power
|
PRC-1235X
|
9033
|
|
Power
|
PRC-1250S
|
6222
|
|
Power
|
PRC-1250X
|
6484
|
|
Power
|
PRC-1250XL
|
7253
|
|
Power
|
PRC-1290X
|
4868
|
|
Power
|
PRC-12100X
|
4778
|
|
Power
|
PRC-12150X
|
3307
|
|
Power
|
SLF-12105
|
4764
|
|
Power
|
SLF-12205
|
2126
|
|
Power
|
TC-1250X
|
14181
|
|
Power
|
TC-1250XL
|
6594
|
|
Power
|
TC-12100X
|
10833
|
|
Power
|
TX-1280X
|
6341
|
|
Tudor
|
|
|
|
Tudor
|
LP105
|
2846
|
|
Yuasa
|
|
|
|
Yuasa
|
NP12-18
|
13704
|
|
Yuasa
|
NPG18-12FR
|
15099
|
|
Yuasa
|
NPX38
|
9309
|
|
Yuasa
|
NPX100R
|
13396
|
|
Yuasa
|
NPX150
|
8799
|
|
Yuasa
|
NPX150-12R
|
8464
|
|
Yuasa
|
NPX150R
|
8535
|
|
Yuasa
|
DM55-12FR
|
7311
|
|